IDProjectCategoryView StatusLast Update
000096710000-009: Alarms and Conditionspublic2011-04-19 17:38
ReporterMatthias Damm Assigned ToPaul Hunkar  
PrioritynormalSeverityminorReproducibilityalways
Status closedResolutionfixed 
Summary0000967: Need clarification about status codes for Read access to Condition fields
Description

At the moment it is not clear what a Read of Condition variables should return if the Quality of the Condition is Bad, e.g. no connection to the underlying system.

The only place where we are talking about status of variable values is if the Condition is disabled.

Optionn 1:
Since Condition events will provide the last value and just the quality field indicates the Bad status, data values should also provide these last event values with good status.

Option 2:
All fields coming from the underlying system provide bad status when reading them.

TagsNo tags attached.
Commit Version
Fix Due Date

Relationships

related to 0001254 closedPaul Hunkar Clarifications regarding connection problems to underlying system 

Activities

Matthias Damm

2010-06-08 22:59

developer   ~0001851

UA phone conference June 8, 2010

Agreed on Option (2).
Need to add a clarification to the spec.

An informative appendix should be created that describes the behaviour in error secnarios. See also related Mantis issue.

Randy Armstrong

2011-04-19 17:38

administrator   ~0002603

Discussed in telecon.

Issue History

Date Modified Username Field Change
2010-02-16 17:17 Matthias Damm New Issue
2010-06-08 22:59 Matthias Damm Note Added: 0001851
2010-06-08 23:11 Matthias Damm Relationship added related to 0001254
2010-11-16 17:41 Randy Armstrong Status new => assigned
2010-11-16 17:41 Randy Armstrong Assigned To => Paul Hunkar
2011-04-19 17:38 Randy Armstrong Status assigned => closed
2011-04-19 17:38 Randy Armstrong Note Added: 0002603
2011-04-19 17:38 Randy Armstrong Resolution open => fixed